Intel study shows data centres need not be cool

  • Email a Friend
  • Print Page
Intel study shows data centres need not be cool
By Iain Thomson
Sep 22, 2008 7:19 AM
Tags: air | centre | data | per | cent | centres

Intel's pilot study on data centre cooling has shown that systems architects may be over-specifying data centre operations.

Intel set up a trial data centre (PDF) of 900 blade servers split into two sections. One side was run in the traditional manner, with air-conditioners and dust filters, and the other used an air economiser which simply sucked out hot air and replaced it with outside air at normal temperature without adjusting for temperature or humidity.

The results were surprising. The unfiltered, un-cooled data centre machines suffered a failure rate of 4.46 per cent, compared to 3.83 per cent for the air conditioned centre, despite having an internal air temperature of around 90 degrees Fahrenheit.

Air in the un-cooled centre was passed through simple household dust filters. The servers became covered with a thick layer of dust over the 10-month trial period but this did not seem to affect reliability.

If the results are extrapolated to a 10-megawatt data centre, Intel estimates that it could cut power consumption by 67 per cent, yielding a cost saving of $2.87m per annum.

"A data centre equipped with an air economiser could substantially reduce Intel's environmental footprint by reducing consumption of power and water," said Don Atwood, regional data centre manager at Intel Information Technology.

"In dry climates, traditional air-conditioned data centres typically include evaporative cooling using water towers as a pre-cooling stage.

"With an economiser, this would not typically be used, potentially saving up to 76 million gallons of water annually in a 10-megawatt data centre."

The test centre was set up in a dry, temperate desert and the results suggest that data centres are capable of operating perfectly well at temperatures approaching 90 degrees Fahrenheit and using much less expensive air conditioning equipment.

The company is now planning on building a 1-megawatt test facility and conducting a longer trial to get a more accurate picture of reliability rates.

 

Copyright © 2009 vnunet.com

 


Comments

Be the first to comment on this article.
Thoughts on this article? Add a comment below.
Comment:
Want to participate in the discussion?
Or log in now to comment


Top Stories
iPhone vulnerable to hackers
Flaw could allow hackers to remotely execute code.
 
Conroy opens NBNCo regulation debate
Part two of the regulatory reforms paper.
 
ShoreTel on recruitment drive for partners
ShoreTel has signed a UC system deal with Cooma-Monaro Shire Council in New South Wales saving the company more than $20,000 annually on telephony costs.
 

Shortcutsall you need to know on...

  • NBN 
  • Windows 7 
  • Unified Communications 
  • Twitter 
  • Virtualisation 

Latest Comments

"Hi Cecil, Tony Lagan from Sony made it clear that is the very case. Thanks for your input. "
by lguan Jul 1, 2009 6:33 PM
 
"Cool, I shall jump in my DeLorean right away, and head off to the Google developer day :-) Back ..."
by jgcertified Jun 30, 2009 10:11 PM
 
"A key issue for organisations is the complexity of licensing, particularly with the wide range ..."
by easysam Jun 30, 2009 6:50 PM
 
"All these $150-$200 predictions assume that $40 million will be paid by home and small business ..."
by peterh_oz Jun 30, 2009 5:06 PM
 
"I read eon below link unencrypting takes along time and another limitation appears to be if ..."
by kWAT Jun 30, 2009 9:56 AM
 

Polls

Has dealing with email security become easier?


   |   View results
The war on junk viruses is never ending, just when one thing is fixed another pops up
  38%
 
Hardware and software has become better at dealing with spam, fake email and virus attachments
  42%
 
Users are the key to dealing with email deluge they just need to be smarter about it
  21%
TOTAL VOTES: 53

Vote now

CRN Magazine

Issue: 268 | June, 2009

CRN Magazine looks in-depth at the emerging issues and developments for the Channel, and provides insight, analysis and strategic information to help resellers better run their businesses.